The KFM3XE series intelligent molded case circuit breakers belong to the KFM3X family and are developed with advanced design and manufacturing technology. Rated insulation voltage is 1000 V; they apply to AC 50 Hz (60 Hz on request) circuits with rated operational voltage 690 V and below and rated operational current up to 800 A, for infrequent conversion and infrequent motor starting.

The KFM3XE series intelligent molded case circuit breakers belong to the KFM3X family and are developed with advanced design and manufacturing technology. Rated insulation voltage is 1000 V; they apply to AC 50 Hz (60 Hz on request) circuits with rated operational voltage 690 V and below and rated operational current up to 800 A, for infrequent conversion and infrequent motor starting.
Protection functions cover long-time inverse overload, short-time inverse and definite-time short delay, instantaneous short circuit and undervoltage; earth-fault protection is optional. The frame current transformer self-powers the controller — protection is reliable from 0.2 In of a single phase.
| Key technical data | Value | Source |
|---|---|---|
| Frame sizes | 125/160/250/400/630/800, plus KFM3E-1600 | P34 |
| Rated operational voltage Ue | AC690V and below | P32 |
| Protection functions | Long-time inverse overload, short-time inverse & definite-time short delay, instantaneous short circuit, undervoltage; earth-fault optional | P32 |
| Self-powered | Protection reliable when single-phase current > 0.2In | P32 |
The full Icu / Ics / Icm matrix per voltage level is available from the original catalog and on request. Values below are summary figures verified against the catalog.


| Frame sizes | Note | Source |
|---|---|---|
| KFM3XE-125 | — | P32–P34 |
| KFM3XE-160 | — | P32–P34 |
| KFM3XE-250 | — | P32–P34 |
| KFM3XE-400 | Draw-out device available | P32–P34 |
| KFM3XE-630 | — | P32–P34 |
| KFM3XE-800 | Draw-out device available | P32–P34 |
| KFM3E-1600 | Separate frame; no 4P, no communication | P33–P34 |
LCD intelligent controller with intuitive settings; the KFM3E-1600 frame uses a knob type.
Source: P33–P37
Includes the PV grid-connection module: undervoltage trip 70%–20% Un, loss-of-voltage trip below 20% Un, overvoltage protection above 135% Un, trip delay adjustable 0–10 s.
Source: P21 / P45 / P67
DC24V / DC110V / DC220V; reliable trip between 70%–110% rated control voltage; 50 cm lead as standard, 100/150 cm optional.
Source: P8 / P38 等
Up to 10 NO + 10 NC independent contacts on KFW3; three-position and ready-to-close contacts optional.
Source: P14–P17
New-generation DC3 mechanism; enables automatic closing with voltage check in PV grid-connection schemes.
Source: P23 / P47 / P69
Two versions available: centre (type CS1) and offset (type CS2).
Source: P50 附近
Ordering codes in the catalog (P53). Specify frame, rated current, poles, controller type and accessory codes.